Mitsubishi Electronics FR-E5NC Marine Battery User Manual


 
HOW TO CHECK FOR ERROR USING THE LEDS
52
LED States
Inverters (FR-E5NC)
Master
unit
Station 1 Station 2 Station 3
Cause Corrective Action
L. RUN
"
SD
"
RD
"
L. ERR
$
L. RUN
"
SD
"
RD
"
L. ERR
"
L. RUN
"
SD
"
RD
"
L. ERR
$
Since the L.ERR LED of the FR-E5NC on station
2 is on, the FR-E5NC itself on station 2 is
affected by noise. (L.RUN may go off.)
Securely connect FG of each
inverter and master unit to ground.
L. RUN
"
SD
"
RD
"
L. ERR
$
L. RUN
"
SD
"
RD
"
L. ERR
"
L. RUN
"
SD
"
RD
"
L. ERR
"
Since the L.ERR LEDs of the FR-E5NCs on
station 2 and later are on, the transmission cable
between the inverters of stations 2 and 3 is
affected by noise. (L.RUN may go off.)
Check that the transmission cable
is connected to SLD. Also run it as
far away as possible from the
power lines. (100mm or more)
TIME
"
LINE
"
or
TIME
$
LINE
"
L. RUN
"
SD
"
RD
"
L. ERR
$
L. RUN
"
SD
"
RD
"
L. ERR
$
L. RUN
"
SD
"
RD
"
L. ERR
"
Terminal resistors are left unconnected. (L.RUN
may go off.)
Check that the terminal resistors
are connected.
"
: On,
$
: Off,
#
: Flicker,
*
: Any of on, flicker or off