975-0395-01-01 19
Basic Installation Procedures
This guide for use by qualified installers only.
AC Output Connections for the Freedom HF 1000,
Freedom HF 1055, and Freedom HF 1800 models
To make a permanent connection to existing AC wiring:
1. Ensure AC and DC power sources are turned off.
2. Install the required circuit breaker in the inverter distribution panel
receiving AC power from the inverter.
3. Strip a single strand (e.g. Romex) AC output wire, as appropriate.
4. Locate the Line, Ground and Neutral terminals on the AC OUT
terminal labeled as L, G, and N respectively.
5. Using a 3.5mm slot long neck screwdriver, open the WAGO cage
clamp by inserting the tool in the clamp slot for Ground terminal.
6. Insert Ground AC wire into Ground terminal slot on the unit.
7. Repeat steps 5 and 6 for Line and Neutral connections.
8. Connect the other end of the wires to a circuit breaker in the inverter
distribution panel.
AC Output Connections for the Freedom HF 1800 T
Model
1. Ensure AC and DC power sources are turned off.
2. Install the required circuit breaker in the inverter distribution panel
receiving AC power from the inverter.
3. Connect the male PTI cable connector to the AC OUT female PTI
receptacle on the unit.
4. Connect the other end of the wires to a circuit breaker in the inverter
distribution panel.
FREEDOM HF 1000
LGN
AC
OUT
clamp slot
terminal opening
10mm
to circuit
breaker
RESET
FREEDOM HF 1800 T
1800 T
to circuit
breaker