Bosch Appliances D9112 Marine Radio User Manual


 
D9112 Operation & Installation Manual
Page 40
74-06144-000-C 2/96
© 1993-1996 Radionics
Point Assignments
Six switches on each POPIT assign the module to a point number. POPIT switch settings
are found in the
Point Assignment
section of the
D9112 Program Sheet
. See Figure 14.
D9112 Program Record Sheet
The first column on the program record sheet contains the switch settings for the
POPITs. Switches are numbered 1 to 6, left to right. Set switches whose number appears
in the setting to the ON position. Set switches with a dash (-) in the switch position in the
setting to the OFF position. See Figure 14.
The second column contains the translation of the point number into the D8112 ZONEX
format. See
Point User Flag
in the
Panel Wide Parameters
module of the
D9112
Program Entry Guide
(74-06145-000) for an explanation of this feature.
The third column contains the point number as it is displayed at command centers. The
fourth column contains the point index. See the
Point Index Parameters
module in the
D9112 Program Entry Guide
(74-06145-000) for an explanation of the point index.
The fifth column of the record sheet shows the area the point is assigned to. The sixth
column shows the Debounce Count for the point. See
Debounce Count
in the
Point
Assignments
module in the
D9112 Program Entry Guide
(74-06145-000).
The seventh column shows the BFSK report code. It is the point number reported for this
point when the panel is using the BFSK format. The eighth column contains the text
displayed at command centers for the point. The text is transmitted to the receiver when
the panel is using the Modem II format.
Figure 14: D9112 Program Record Sheet