Bosch Appliances D9112 Marine Radio User Manual


 
D9112 Operation & Installation Manual
Page 64
74-06144-000-C 2/96
© 1993-1996 Radionics
System Chart
2+ = Two or more required for this application. Consult the appropriate standard.
1• = At least one detector required. You can substitute other 2-wire detectors listed
for use with the D125. You could also use the D262 with the D270 four-wire
base and a listed power supervision relay.
= Listed bell (siren) housing required for burglary alarm bell or siren.
(Empty Box) = Not used for this application.
* = Auxiliary applies to the D184 Auxiliary Local Energy Interface Kit.
No = Not acceptable for this application
Req. = Required for this application
Opt. = Optional for this application
# = D125 or D129 required to connect fire alarm initiating devices to zones 1 to 8.
D125 provides two powered loops for connecting listed 2-wire smoke detectors.
D129 provides two non-powered Class A initiating circuits.
1+ = One or more required for this application. Consult the appropriate standard.
Central Station Fire
Central Station Fire /
Burglary Combined
Electrically Actuated
Transmitter
Local Fire
Local Fire / Burglary
Combined
Local Burglary
Police Connected
Burglary
Central Station Burglary
(Grade C)
Household Fire /
Burglary Combined
Household Fire
Household Burglary
Local and Central Station
Fire Combined
Local and Central Station
Fire / Burglary (Grade C)
24 +
4 mins
alarm
24 +
4 mins
alarm
4
4
4
4
24 +
5 mins
alarm
60 +
5 mins
alarm
24 +
5 mins
alarm
24 +
5 mins
alarm
24 +
5 mins
alarm
No No
No
No
No No No
No No No
Req.
Req.
Req.
NoNo No
Choose one.
Choose
one
Req.
##
Calculate current draw to determine
if second battery is required.
Calculate current draw to determine
if second battery is required.
Opt. Opt.Opt.
Opt.
1+
1+
1+ 1+ 1+ 1+ 2+ 1+ 1+ 1+ 1+ 1+ 1+ 1+
Opt. Opt.NoNo No
No
Opt.No
Opt. Opt.
NoOpt.
Opt.
##
#
- D125 or D129 required to connect fire alarm initiating
devices to zones1 to 8. D125 provides two powered loops
for connecting listed 2-wire smoke detectors. D129
provides two non-powered Class A initiating circuits.
Opt.
Choose one.
D101 lock required for
enclosure.
2 Req.
Required to connect panel to
RJ31X TelCo Block.
Two Required to connect D128
Module to RJ31X TelCo Blocks.
Required for communication on two phone lines and/or
CPU watchdog function.
Opt. Opt. Opt.Opt. Opt. Opt.
Minimum Hours
of Standby
Battery
D8103 Enclosure
D8108A Enclosure
D8109 Enclosure
D122 Dual Battery
Harness
D125B Powered
Loop Interface
D129 Class A
Initiating Module
D126 Battery
D127 Reversing
Relay
D128 Dual Phone
Line Module
D161 Telephone
Cord
D184 Auxiliary
Interface Kit
D192C Bell Circuit
Supervision
D262 / D260 Smoke
Detector / Base
D268 / D269
Independent
Zone Control
D431, D435, D438,
D440, D442, D448,
Indicating Device
D461 Pull Station
D1255 Command
Center
D1640 Transformer
D8004 Transformer
Enclosure
D8122 Derived
Channel S.T.U.
D8125
POPEX Module
D8127T/U
POPIT Module
D8128A OctoPOPIT
D8129 OctoRelay
D8130 Release
Module
D8132 Battery
Charger
D9131 Printer
Interface
1+ 1+ 1+ 1+
1+
1+,
1+
Required for indicating circuits.
Opt.
Opt.
Opt.
Opt.
Opt.Opt.
Opt.
Opt.
Optional, only connect to zones 1 to 8.
1+
Opt. Opt. Opt.
Optional, may be required by job specification and/or Authority Having Jurisdiction.
Opt. Opt.Opt.Opt.
Opt.
Opt.
Opt.
1+
1+
1+1+ 1+
Opt.
1+
1+
1+ 1+ 1+ 1+
1+
Required for all applications.
Opt.
Opt.
Opt.Opt.
Opt.
Opt.
Required
Opt.Opt. Opt. Opt. Opt.Opt. Opt.
Required for D8127T/U POPITs.
Optional, contact TelCo for availability of derived channel service.
Opt.
Opt.
Opt. Opt.
Opt. Opt.
Optional, for remote annuciation of system functions.
Optional
Optional, use with parallel printer to print events from panel log locally.
See Current Rating Chart and Standby Battery Requirements in D9112 Operation and Installation
Manual to determine if system requires a D8132 module for increased battery standby.
Opt.
Opt.
Opt.
Opt.
No
Opt.
No No Opt.
Opt. No No
No Opt.
Remote Station or
Auxiliary Fire
*
24 +
5 mins
alarm
24 +
5 mins
alarm
24 +
5 mins
alarm