© 1993-1996 Radionics74-06144-000-C 2/96
Table 3: D8129 Switch Settings
D9112
Relay Number
D8129 OctoRelay
Switch Setting
On D9112, connect
D8129 to
1 to 8 Off-On-On-On-On
ZONEX 1
Terminal 28
9 to 16 On- Off-On-On-On
ZONEX 1
Terminal 28
17 to 24 Off- Off-On-On-On
ZONEX 1
Terminal 28
25 to 32 On- On-Off-On-On
ZONEX 1
Terminal 28
33 to 40 Off- On-Off-On-On
ZONEX 1
Terminal 28
41 to 48 On- Off-Off-On-On
ZONEX 1
Terminal 28
49 to 56 Off- Off-Off-On-On
ZONEX 1
Terminal 28
57 to 64 On- On-On-Off-On
ZONEX 1
Terminal 28
65 to 72 Off-On-On-On-On
ZONEX 2
Terminal 26
73 to 80 On- Off-On-On-On
ZONEX 2
Terminal 26
81 to 88 Off- Off-On-On-On
ZONEX 2
Terminal 26
89 to 96 On- On-Off-On-On
ZONEX 2
Terminal 26
97 to 104 Off- On-Off-On-On
ZONEX 2
Terminal 26
105 to 112 On- Off-Off-On-On
ZONEX 2
Terminal 26
113 to 120 Off- Off-Off-On-On
ZONEX 2
Terminal 26
121 to 128 On- On-On-Off-On
ZONEX 2
Terminal 26