LSI AP1172-E1 Life Jacket User Manual


 
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Power Requirements
Command Module and Drive Module Site Preparation Guide 1-9
AC Power Distribution Boxes
The cabinet has two identical AC power distribution boxes with two separate power cords
(Figure 1-4). Depending on the configuration ordered, each box supports either domestic
or international units and includes the following features:
One domestic plug (NEMA L6-30P, 30 A, 220 VAC) or one international plug
(IEC 309, 32 A, 3-pin, 230 VAC)
One circuit breaker (25 A)
Two power outlets (IEC 320, 16 A, C-19, filtered individually for international and
domestic EMC compliance)
Support for up to 12 attachments per box (24 per cabinet) using two ladder cables
(refer to Ladder Cords on page 1-10)
Figure 1-4 Cabinet AC Distribution
AC Power
Distribution Boxes
AC Power Distribution Box
Power Cords