LSI AP1172-E1 Life Jacket User Manual


 
Drive Module Site Preparation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-8 Command Module and Drive Module Site Preparation Guide
Power Requirements
This section provides information regarding drive module AC power requirements, power
cord routing instructions, and site wiring conditions.
The AC power source must provide the correct voltage, current, and frequency specified
on the manufacturers nameplate. Internal AC power units for rackmount cabinets must
be able to handle the power requirements for these units. Refer to Table 3-7, Table 3-8, and
Table 3-9 on page 3-9 for more information.
Table 3-7 FC-1 10x Drive Module Power Requirements
Item Unit of Measure Requirement
Circuit Breaker Slow-blow Fuse 10 A per Power Supply
AC Power
Low Range High Range
Nominal Voltage 90 to 136 VAC 198 to 264 VAC
Frequency 50 to 60 Hz 50 to 60 Hz
Idle Current 3.02 A
1.31 A
1
Maximum Operating Current 3.11 A
1.34 A
1
Maximum Surge Current
(10-drive spin up)
4.70 A
1.92 A
1
1
Typical current: 240 VAC, 60 Hz at 0.70 power efficiency, 0.99 power factor.
Table 3-8 FC-1 14x Drive Module Power Requirements
Item Unit of Measure Requirement
Circuit Breaker Slow-blow Fuse 10 A per Power Supply
AC Power
Low Range High Range
Nominal Voltage 90 to 136 VAC 198 to 264 VAC
Frequency 50 to 60 Hz 50 to 60 Hz
Idle Current
2.95 A
1
1.42 A
2
Maximum Operating Current
3.03 A
1
1.46 A
2
Maximum Surge Current
(14-drive spin up)
4.28 A
1
1.97 A
2
1
Typical current: 115 V AC, 60 Hz at 0.72 power efficiency, 0.99 power factor.
2
Typical current: 230 V AC, 60 Hz at 0.72 power efficiency, 0.99 power factor.