LSI AP1172-E1 Life Jacket User Manual


 
Command Module Site Preparation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-6 Command Module and Drive Module Site Preparation Guide
Environmental Requirements
The command module is designed to operate in the environment defined in Table 2-5 and
Table 2-6.
Table 2-5 Command Module Environmental Requirements
Condition Parameter
Requirement
E4400 E4600 E5600
Temperature
Operating Range
0
°
C to 43
°
C
(32
°
F to 109
°
F)
0
°
C to 40
°
C
(32
°
F to 104
°
F)
Maximum Rate of Change
10
°
C (18
°
F) per hour
Storage Range
-10
°
C to 65
°
C (14
°
F to 149
°
F)
Maximum Rate of Change
15
°
C (27
°
F) per hour
Transit Range
-40
°
C to 60
°
C
(-40
°
F to 140
°
F)
-40
°
C to 65
°
C
(-40
°
F to 149
°
F)
Maximum Rate of Change
20
°
C (36
°
F) per hour
Relative Humidity
No condensation
Operating Range 10% to 90% 20% to 80%
Storage Range 10% to 93%
Transit Range 5% to 95%
Maximum Dew Point
26
°
C (79
°
F)
Maximum Gradient 10% per hour
Sound
Sound Power 6.5 bels
Sound Pressure 65 dBA
Altitude
(Above Sea Level)
1
Operating and Storage
3000 m (9840
ft.)
3048 (10,000 ft.)
Transit 12,000 m (40,000 ft.)
Altitude
(Below Sea Level)
Operating, Storage,
and Transit
30.5 m (100 ft.)
1
If you plan to operate a command module at altitudes between 1000 m to 3000 m (3280 ft. to 9850 ft.) above sea level,
lower the environmental temperature 1.7
°
C (3.3
°
F) for every 1000 m (3280 ft.) above sea level.