1-10 Command Module and Drive Module Site Preparation Guide
Ladder Cords
Each AC power distribution box outlet supports one ladder cord (Figure 1-5) that you can
connect to a maximum of six modules. You may connect up to twelve 220/230 VAC
modules to each AC power distribution box for a maximum of twenty-four power
attachments inside the cabinet.
Although the cabinet may not be fully populated when shipped, the cabinet is shipped with
two ladder cords. Each cord has the following specifications:
Cord 10 A per cord (1.67 A per connection if all are used)
Input Connector IEC 320, C-19, 16 A, 250 VAC
Plugs IEC 320, C-14, 10 A, 250 VAC
Ladder Step 5.25 inches between connections
Cord Routing Route cords between the mounting rails and side skins of cabinet
Figure 1-5 Cabinet Ladder Cord