Q Selection of wiring equipment
No-fuse breaker (MCCB) Magnetic contactor (MC) Applicable motor
(kW)
Inverter type form Input current [A]
Rated current [A] Rated current [A] AC-1
0.75 VFPS1-4007PLE/PDE 1.8 4 25
1.5 VFPS1-4015PLE/PDE 3.5 6.3 25
2.2 VFPS1-4022PLE/PDE 5 10 25
3.7 VFPS1-4037PLE/PDE 8.8 14 25
5.5 VFPS1-4055PLE/PDE 11.4 25 25
7.5 VFPS1-4075PLE/PDE 15.8 25 25
11 VFPS1-4110PLE/PDE 21.9 30 32
15 VFPS1-4150PLE/PDE 30.5 40 40
18.5 VFPS1-4185PLE/PDE 37.5 60 50
22 VFPS1-4220PLE/PDE 43.6 60 50
30 VFPS1-4300PLE/PDE 56.7 100 80
37 VFPS1-4370PLE/PDE 69.5 100 125
45 VFPS1-4450PLE/PDE 85.1 125 125
55 VFPS1-4550PLE/PDE 104.8 150 125
75 VFPS1-4750PLE/PDE 140.3 200 250
90 VFPS1-4900PLE/PDE 171.8 200 250
(*1): Selections for use of the Toshiba 4-pole standard motor with power supply voltage of 400V-50Hz.
(*2): Choose the MCCB according to the power supply capacity.
For comply with UL and CSA standard, use the fuse certified by UL and CSA.
(*3): When using on the motor side during commercial-power supply operation, choose the MC with class AC-3 rated
current for the motor rated current.
(*4): Attach surge killers to the magnetic contactor and exciting coil of the relay.
(*5): In the case the magnetic contactor (MC) with 2a-type auxiliary contacts is used for the control circuit, raise the
reliability of the contact by using 2a-type contacts in parallel connection.