Xantrex Technology 809-0915 Marine RADAR User Manual


 
975-0082-01-01 9
Xanbus Automatic Generator Start Installation
Routing Connections
Connection Types Because the AGS will be part of a Xanbus system, it
is necessary to consider how to route two types of connections:
connections to the generator, thermostats, and other external devices
and switches, using the included 20-contact connector and wiring
harness.
connections to other Xanbus-enabled devices, using network cables.
EXPLOSION HAZARD
This equipment is not ignition protected. To prevent fire or explosion, do
not install the AGS in locations that require ignition-protected equipment.
This includes any space containing gasoline-powered machinery, fuel
tanks, as well as joints, fittings, or other connections between
components of a fuel system.
Follow all relevant instructions exactly before installing or using your
AGS.
SHOCK AND ENERGY HAZARDS
Before making any connections to the generator, ensure that the
generator’s starter is disabled and the generator’s start battery is
disconnected.
Failure to follow these instructions will result in death or serious
injury.
Figure 5
AGS External Connections
Wiring harness
(connection to
generator,
thermostats, and
external switches)
Network cables
to other Xanbus-
enabled devices
20-contact
connector
Network ports