18 Xanbus Automatic Generator Start (AGS) Owner’s Guide
Xanbus Automatic Generator Start Installation
Type 4
Type 4 is a three-wire StartStop configuration that uses relay 3 to provide a
60-second preheat signal.
Figure 10
Type 4 Connection Diagram
Relay Function Preset Configuration Setting
Relay 1 mode StartStop
Relay 3 mode Preheat
Gen Run signal hold time 10 s
Preheat time 60 s
AGS HarnessWires
Generator Wires
18
17
16
14
13
12
20
19
FUEL PRIME (PREHEAT)
12V GENERATOR BATTERY+
Relay 1
Relay 3
Relay 2
5Afuse
5Afuse
5Afuse
GENERATOR RUN SIGNAL
STOP/PREHEAT
START
GENERATOR RUN SIGNAL RETURN
For additional information, see “Circuit Limitations” on page 11.
Preheat to crank delay 5 s
Crank time 15 s
Crank retry time 15 s
Gen Cool Down 30 s
Gen Spin Down 3 s
Shutdown bypass time 0 s
Start tries 3
Relay Function Preset Configuration Setting