84 Xanbus Automatic Generator Start (AGS) Owner’s Guide
Appendix B: Relay Timing
GlowStop Mode
For generators with GlowStop mode starting types (Types 1, 2, 3, 6, 12):
Relay 1 (Stop) and Relay 2 (Start) can be used with a common ground
for three-wire configured generators.
The Preheat signal shows up on Relay 1 and also Relay 3 (if enabled)
so that Relay 1 can be used for both Preheat and Stop.
If the ShutDown Bypass is enabled, the Preheat on Relay 1 will remain
high for the Crank Time and for the ShutDown Bypass period after
cranking.
The Preheat on Relay 3 will only overlap the Crank Time and perform
ShutDown Bypass if Relay 3 is configured for Preheat with ShutDown
Bypass.
The “Delay” refers to the “Preheat to Crank Delay” and may be zero.
Cranking will cease when the generator run signal goes high for the
specified hold time or when the crank time has elapsed.
Figure 39
GlowStop Mode Timing Diagram
Relay 1: Glow/Stop
Relay 2: Start
(Cranking)
Relay 3: Preheat
(Glow)
Start
Run
Stop
Preheat
Delay
Crank
Time
Preheat/
Stop
Shutdown
Bypass