975-0082-01-01 49
Configuration of the Xanbus AGS
Stop V
Full name Stopping Battery Voltage
Purpose The "Stop V" trigger enables the AGS to stop the generator
whenever the battery voltage reaches a pre-set DC voltage. Whenever the
generator starts automatically based on the Starting Battery Voltage, it will
shut off once the Stopping Battery Voltage has been reached.
Dependencies The "Stop V" trigger requires the AGS to be in
Automatic mode and needs a parameter to be set for one of the Start DCV
triggers.
Considerations The "Stop V" setting is most useful when you want the
inverter/charger to give the batteries a quick, basic charge. If using this
mode, it is recommended to run a complete charge or equalize cycle once in
a while to restore the battery. To give the batteries a more complete,
consistent charge, use the "Stop Float" setting. This will result in longer
generator run times.
If "Stop V" is set too high, the generator may run for too long.
If "Stop V" is set too low, the AGS will stop the generator before the
inverter/charger has charged the batteries.
If "Stop Float" or "Stop Absorb" have been enabled, the AGS will
stop the generator if the Float or Absorption stages of the battery charging
have begun.
Actual battery voltage can be monitored from the Freedom SW System
Home screen on the Xanbus System Control Panel (SCP).
For more information on battery charging, see the Freedom SW Inverter/
Charger Owner’s Guide.
Values Default
Disabled, 14.0 V to 60.0 V
(increments of 0.1 V)
Disabled