Xantrex Technology 809-0915 Marine RADAR User Manual


 
975-0082-01-01 23
Xanbus Automatic Generator Start Installation
Type 9
Type 9 is a StartStop mode configuration with shutdown bypass
functionality on relay 3.
Figure 17
Type 9 Connection Diagram
Relay Function Preset Configuration Setting
Relay 1 mode StartStop
Relay 3 mode Shutdown Bypass
Gen Run signal hold time 0.5 s
Preheat time 0 s
Preheat to crank delay 0 s
AGS Harness Wires Generator Wires
18
17
16
14
13
12
20
19
FUEL PRIME (PREHEAT)
12V GENERATOR BATTERY+
Relay 1
Relay 3
Relay 2
5A fuse
5A fuse
5A fuse
GENERATOR RUN SIGNAL
STOP
START
GENERATOR RUN SIGNAL RETURN
For additional information, see “Circuit Limitations” on page 11.
Crank time 15 s
Crank retry time 30 s
Gen Cool Down 30 s
Gen Spin Down 3 s
Shutdown bypass time 5 s
Start tries 3
Relay Function Preset Configuration Setting