Configuration of the Xanbus AGS
When the AGS Home Screen is first displayed, the menu defaults to the
GenMode Menu. If configuration changes need to be made, the
Configuration Menu can be accessed by pressing the Enter, Up arrow, and
Down arrow buttons all at same time to access the Advanced Settings.
Figure 32
AGS Configuration Menu Contents
Xanbus System Control Panel (SCP)
FGA: 809-0921
AC In/Charge
Inverter On
Low Battery
Fau lt
STBY/ON
FaultClear
TM
Enter Func
XAGS 00: Setup
Mode
Clear Faults Warnings
View Device Info
[Operating]
GenMode [ManualOff]
Use these buttons to select
the desired menu.
XanbusAGS Menu
Press ENTER to move the cursor
to the changeable settings.
Use these buttons to
change the settings.
Press ENTER to accept
the new setting.
To access theAdvanced Settings menu,
Press Enter and Up and Down arrows together
To return to the B asic Settings menu,
Press Enter and Up and Down arrows together
Press Enter to move forward
into the Config menu.
To change configuration parameters...
Press Func to return to the
Xanbus AGS Home screen.
XAGS 00: Setup
Clear Faults Warnings
View Device Info
Advanced Settings
GenMode [ManualOff]
XAGS 00: Setup
Clear Faults Warnings
View Device Info
GenMode [ManualOff]
XAGS 00: Triggers
Start DCV 15 Sec
Start DCV 2 hr
Start DCV 24 Hr
[Disabled]
[Disabled]
[Disabled]
Start DCV 30 Sec [40.0V]
Stop Absorb
StopV
Temp1
[Disabled]
[Disabled]
[Disabled]
Stop Float [Disabled]
Load
Start Load
Stop Load
[Disabled]
[15A]
[10A]
Temp2 [Disabled]
XAGS 00: Gen
Gen Cool Down
Gen Spin Down
Max Runtime
[30sec]
[3sec]
[4hours]
Starter Cool Down [60sec]
Exercise Dur
Exercise Time
Relay 3
[30min]
[9:00AM]
[Not Used]
Exercise per [21days]
Crank Delay
Crank Time
Crank Retry Time
[1sec]
[30sec]
[40sec]
Preheat Time
Gen Start Tries
[0sec]
[3]
Gen Run Hold Time [0.5s]
XAGS 00: Gen
Dev Number
Connections
[00]
Dev Name [AGS]
Advanced Settings
XAGS 00: Config
QT Begin
QT End
QT EN [Enabled]
[9:00PM]
[8:00AM]
Gen Type [2]
Cfg Trigger
Cfg Gen
Multi-Unit Config
Restore Defaults
XAGS 00: Conn
AC In
AC Out
[Grid1]
[ACLoad]
Generator [Gen1]
DC Conn [HouseBatt1]