Appendix B: Relay Timing
StartStop Mode
For generators with StartStop mode starting types (Types 4, 5, 9, 10):
Relay 1 (Stop) and Relay 2 (Start) can be used with a common ground
for three-wire configured generators.
If Relay 3 is configured for preheat, the signal only shows up on Relay
3.
The Preheat on Relay 3 will not overlap the Crank Time if ShutDown
Bypass is not enabled.
If the ShutDown Bypass is enabled, the Preheat on Relay 3 will remain
high for the Crank Time and for the ShutDown Bypass period after
cranking.
The “Delay” refers to the “Preheat to Crank Delay” and may be zero.
Cranking will cease when the generator run signal goes high for the
specified hold time or when the crank time has elapsed.
To get the ShutDown Bypass on Relay 3 with no preheat, Relay 3 must
be configured for Preheat with ShutDown Bypass and have the Preheat
time set to zero.
StartStop mode is essentially the same as GlowStop mode with no
preheat on Relay 1.
Figure 40
StartStop Mode Timing Diagram
Relay 1: Stop
Relay 2: Start (Cranking)
Relay 3: Preheat (Glow)
& Shutdown Bypass
Start
Stop
Preheat
Delay
Crank
Time
Shutdown
Bypass