22 Xanbus Automatic Generator Start (AGS) Owner’s Guide
Xanbus Automatic Generator Start Installation
Type 8
Type 8 will work with both two-wire and three-wire run mode
configurations. Type 8 is identical to Type 7 except that it provides no
preheat signal before cranking.
Figure 15
Type 8 Connection Diagram (two-wire)
Figure 16
Type 8 Connection Diagram (three-wire)
AGS Harness Wires Generator Wires
16
14
13
12
Relay 1
5A fuse
GENERATORRUN SIGNAL
GENERATORRUN SIGNAL RETURN
RUN
For additional information, see “Circuit Limitations” on page 11.
AGS HarnessWires Generator Wires
GENERATORRUN SIGNAL
GENERATORRUN SIGNAL RETURN
RUN
18
17
16
14
13
12
Relay1
Relay2
5A fuse
5A fuse
START
For additional information, see “Circuit Limitations” on page 11.
Relay Function Preset Configuration Setting
Relay 1 mode Run
Relay 3 mode No function
Gen Run signal hold time 0.5 s
Preheat time 0 s
Preheat to crank delay 0 s
Crank time 15 s
Crank retry time 30 s
Gen Cool Down 30 s
Gen Spin Down 3 s
Shutdown bypass time 0 s
Start tries 3