Emerson Rosemount 3051CF Marine Instruments User Manual


 
June 2014
14
Quick Start Guide
When the user exits the “Locate Device” method, the device LCD display
automatically returns to normal operation.
Note
Some hosts do not support “Locate Device” in the DD.
Step 6: Configure
Each FOUNDATION fieldbus host or configuration tool has a different way of
displaying and performing configurations. Some use Device Descriptions (DD) or
DD methods for configuration and to display data consistently across platforms.
There is no requirement that a host or configuration tool support these features.
Use the following block examples to do basic configuration to the transmitter. For
more advanced configurations see the 3051 reference manual (document
number 00809-0100-4774, Rev. CA or newer).
Note
DeltaV users should use DeltaV Explorer for the Resource and Transducer blocks and Control
Studio for the Function Blocks.
Configure the AI block
If your configuration tool supports Dashboard DD's or DTM's you may use either
guided setup or manual setup. If your configuration tools don't support
Dashboard DD's or DTM's, use manual setup. Navigation instructions for each
step are provided below. In addition the screens used for each step are shown in
Figure 11, Basic Configuration Menu Tree.
Figure 10. Configuration Flowchart
Start
Device Configuration
Here
1. Verify Device Tag:
PD_TAG
7. Set Damping:
PRIMARY_VALUE_
DAMPING
8. Set up LCD Display
6. Set Low Cutoff:
LOW_CUT
9. Review Transmitter
Configuration
3. Set Signal
Conditioning:
L_TYPE
5. Set Scaling
OUT_SCALE
2. Check Switches and
Software Write Lock
Done
10. Set Switches and
Software Write Lock
4. Set Scaling
XD_SCALE
00825-0100-4774_RevFA.fm Page 14 Friday, June 6, 2014 2:21 PM