June 2014
16
Quick Start Guide
a. Navigation: from the overview screen, select “Device Information” and then
select the “Security and Simulation” tab.
b. Perform “Write Lock Setup” to disable Software Write Lock.
Note
Place the control loop in “Manual” mode before beginning Analog Input Block
configuration.
AI block configuration
1. To use guided setup:
a. Navigate to Configure, then Guided Setup.
b.Select “AI Block Unit Setup”.
Note
Guided setup will automatically go through each step in the proper order.
2. To use manual setup:
a. Navigate to Configure, Manual Setup, then Process Variable.
b.Select “AI Block Unit Setup”.
c. Place the AI Block in “Out of Service” mode.
Note
When using manual setup perform the steps in the order described in the "Configure
the AI block".
Note
For convenience, AI Block 1 is pre-linked to the transmitter primary variable and should
be used for this purpose. AI Block 2 is pre-linked to the transmitter sensor temperature.
The channel must be selected for AI Blocks 3 and 4.
Channel 1 is the primary variable.
Channel 2 is the sensor temperature.
If the FOUNDATION fieldbus Diagnostics Suite Option Code D01 is enabled, these
additional channels are available.
Channel 12 is the SPM mean.
Channel 13 is the SPM standard deviation.
To configure SPM refer to the 3051 FOUNDATION fieldbus users' manual
Document number 00809-0100-4774.
Note
Step 4
through Step 7 are all performed in a single step by step method under guided
setup, or on a single screen using manual setup.
00825-0100-4774_RevFA.fm Page 16 Friday, June 6, 2014 2:21 PM