Quick Start Guide
19
June 2014
AI block configuration parameters
Use the Pressure, DP Flow, and DP Level examples for guides.
Pressure example
DP Flow example
Parameters Enter data
Channel 1=Pressure, 2=Sensor Temp, 12=SPM mean, 13=SPM standard deviation
L-Type Direct, Indirect, or Square Root
XD_Scale Scale and Engineering Units
Note
Select only the
units that are
supported by the
device.
Pa bar torr @ 0 °C ft H
2
0 @ 4°C m H
2
0 @ 4 °C
kPa mbar kg/cm
2
ft H
2
0 @ 60 °F mm Hg @ 0 °C
mPa psf kg/m
2
ft H
2
0 @ 68 °F cm Hg @ 0 °C
hPa Atm in H
2
0 @ 4°C mm H
2
0 @ 4 °C in Hg @ 0 °C
Deg C psi in H
2
0 @ 60 °F mm H
2
0 @ 68 °C m Hg @ 0 °C
Deg F g/cm
2
in H
2
0 @ 68 °F cm H
2
0 @ 4 °C
Out_Scale Scale and Engineering Units
Parameters Enter data
Channel 1
L_Type Direct
XD_Scale See list of supported engineering units.
Note
Select only the units that are supported by the device.
Out_Scale Set values outside operating range.
Parameters Enter data
Channel 1
L_Type Square Root
XD_Scale 0 - 100 inH
2
0 @ 68 °F
Note
Select only the units that are supported by the device.
Out_Scale 0 - 20 GPM
Low_Cut inH
2
0 @ 68 °F
00825-0100-4774_RevFA.fm Page 19 Friday, June 6, 2014 2:21 PM