March 2014 Quick Start Guide
3051 Product Certifications
Rev 1.0
European Directive Information
A copy of the EC Declaration of Conformity can be found at the end of the Quick Start Guide.
The most recent revision of the EC Declaration of Conformity can be found at
www.rosemount.com.
Ordinary Location Certification from FM Approvals
As standard, the transmitter has been examined and tested to determine that the design
meets the basic electrical, mechanical, and fire protection requirements by FM Approvals, a
nationally recognized test laboratory (NRTL) as accredited by the Federal Occupational
Safety and Health Administration (OSHA).
North America
E5 FM Explosionproof (XP) and Dust-Ignitionproof (DIP)
Certificate: 0T2H0.AE
Standards: FM Class 3600 – 1998, FM Class 3615 – 2006, FM Class 3810 – 2005,
ANSI/NEMA 250 – 2003
Markings: XP CL I, DIV 1, GP B, C, D; DIP CL II, DIV 1, GP E, F, G; CL III; T5(-50°C Ta
+85°C); Factory Sealed; Type 4X
I5 FM Intrinsic Safety (IS) and Nonincendive (NI)
Certificate: 1Q4A4.AX
Standards: FM Class 3600 – 1998, FM Class 3610 – 2010, FM Class 3611 – 2004, FM Class
3810 – 2005
Markings: IS CL I, DIV 1, GP A, B, C, D; CL II, DIV 1, GP E, F, G; Class III; DIV 1 when
connected per Rosemount drawing 03031-1019; NI CL 1, DIV 2, GP A, B, C, D;
T4(-50°C Ta +70°C) [HART], T5(-50°C Ta +40°C) [HART]; T4(-50°C Ta
+60°C) [Fieldbus/PROFIBUS]; Type 4x
Special Conditions for Safe Use (X):
1. The Model 3051 transmitter housing contains aluminum and is considered a potential
risk of ignition by impact or friction. Care must be taken into account during installation
and use to prevent impact and friction.
2. The Model 3051 transmitter with the transient terminal block (Option code T1) will not
pass the 500Vrms dielectric strength test and this must be taken into account during
installation
IE FM FISCO
Certificate: 1Q4A4.AX
Standards: FM Class 3600 – 1998, FM Class 3610 – 2010, FM Class 3611 – 2004, FM Class
3810 – 2005
Markings: IS CL I, DIV 1, GP A, B, C, D when connected per Rosemount drawing 03031-
1019 (-50°C Ta +60°C); Type 4x
Special Conditions for Safe Use (X):
1. The Model 3051 transmitter housing contains aluminum and is considered a potential
risk of ignition by impact or friction. Care must be taken into account during installation
and use to prevent impact and friction.
2. The Model 3051 transmitter with the transient terminal block (Option code T1) will not
pass the 500Vrms dielectric strength test and this must be taken into account during
installation
C6 CSA Explosionproof, Dust-Ignitionproof, Intrinsic Safety and Nonincendive
Certificate: 1053834
Standards: ANSI/ISA 12.27.01-2003, CSA Std. C22.2 No. 30 -M1986, CSA Std. C22.2
No.142-M1987, CSA Std. C22.2. No.157-92, CSA Std. C22.2 No. 213 - M1987