Mitsubishi Electronics FR-D700-G Outboard Motor User Manual


 
13
Wiring
2
zWire removal
(3) Control circuit common terminals (SD, 5, SE)
Terminals SD, SE and 5 are common terminals for I/O signals.(All common terminals are isolated from each other.) Do not
earth them. Avoid connecting the terminals SD and 5 and the terminals SE and 5.
Terminal SD is a common terminal for the contact input terminals (STF, STR, RH, RM, RL) and pulse train output terminal
(FM). The open collector circuit is isolated from the internal control circuit by photocoupler.
Terminal 5 is a common terminal for the speed setting signals (terminals 2 or 4). It should be protected from external noise
using a shielded or twisted cable.
Terminal SE is a common terminal for the open collector output terminal (RUN). The contact input circuit is isolated from the
internal control circuit by photocoupler.
(4) Wiring instructions
1)It is recommended to use the cables of 0.3mm
2
to 0.75mm
2
gauge for connection to the control circuit terminals.
2)The maximum wiring length should be 30m (200m for terminal FM).
3)Do not short across terminals PC and SD. Drive unit may be damaged.
4)Use two or more parallel micro-signal contacts or twin contacts to prevent
contact faults when using contact inputs since the control circuit input signals
are micro-currents.
5)Use shielded or twisted cables for connection to the control circuit terminals
and run them away from the main and power circuits (including the 200V relay
sequence circuit).
6)Do not apply a voltage to the contact input terminals (e.g. STF) of the control
circuit.
7)Always apply a voltage to the fault output terminals (A, B, C) via a relay coil, lamp, etc.
3) Insert the wire into a socket.
When using a single wire or a stranded wire without a blade terminal, push an
open/close button all the way down with a flathead screw driver, and insert the wire.
NOTE
y When using a stranded wire without a blade terminal, twist enough to avoid short circuit with a nearby terminals or
wires.
y Place the flathead screwdriver vertical to the open/close button. In case the blade tip slips, it may cause damage to
drive unit or injury.
Pull the wire with pushing the open/close button all the
way down firmly with a flathead screwdriver.
Open/close button
Flathead screwdrive
r
Open/close button
Flathead screwdrive
r
NOTE
y Pulling out the terminal block forcefully without pushing
the open/close button all the way down may damage the
terminal block.
y Use a small flathead screwdriver (Tip thickness: 0.4mm/
tip width: 2.5mm).
If a flathead screwdriver with a narrow tip is used,
terminal block may be damaged.
Products available on the market :(as of January 2010)