Mitsubishi Electronics FR-D700-G Outboard Motor User Manual


 
28
Parameter list
6.2 Parameter list
REMARKS
y indicates simple mode parameters.
y The parameters surrounded by a black border in the table allow its setting to be changed during operation even if "0" (initial
value) is set in Pr. 77 Parameter write selection.
Parameter
Name
Setting
Range
Initial
Value
1 Maximum setting
0 to12000r/min/
0 to 8000r/min *
1
3000r/min
2 Minimum setting
0 to 3600r/min/
0 to 2400r/min *
1
0r/min
4
Multi-speed setting (high
speed)
0 to 12000r/min/
0 to 8000r/min *
1
3000r/min
5
Multi-speed setting (middle
speed)
0 to 12000r/min/
0 to 8000r/min *
1
1500r/min
6
Multi-speed setting (low
speed)
0 to 12000r/min/
0 to 8000r/min *
1
300r/min
7 Acceleration time 0 to 3600s 5s
8 Deceleration time 0 to 3600s 5s
9 Electronic thermal O/L relay 0 to 500A
Rated
motor
current
10 Coasting speed
0 to 3600r/min/
0 to 2400r/min *
1
90r/min
11
DC injection brake operation time
0 to 10s 0.5s
13 Starting speed
0 to 1800r/min/
0 to 1200r/min *
1
15r/min
15 Jog speed setting
0 to 12000r/min/
0 to 8000r/min *
1
150r/min
16
Jog acceleration/deceleration
time
0 to 3600s 0.5s
17 MRS input selection 0, 2, 4 0
20
Acceleration/deceleration
reference speed
30 to 12000r/min/
20 to 8000r/min *
1
3000r/min
22 Stall prevention operation level 0 to 200% 150%
24 Multi-speed setting (speed 4)
0 to 12000r/min/
0 to 8000r/min *
1
,
9999
9999
25 Multi-speed setting (speed 5)
0 to 12000r/min/
0 to 8000r/min *
1
,
9999
9999
26 Multi-speed setting (speed 6)
0 to 12000r/min/
0 to 8000r/min *
1
,
9999
9999
27 Multi-speed setting (speed 7)
0 to 12000r/min/
0 to 8000r/min *
1
,
9999
9999
29
Acceleration/deceleration
pattern selection
0, 1, 2 0
30
Regenerative function selection
0, 1 0
31 Speed jump 1A
0 to 12000r/min/
0 to 8000r/min *
1
,
9999
9999
32 Speed jump 1B
0 to 12000r/min/
0 to 8000r/min *
1
,
9999
9999
33 Speed jump 2A
0 to 12000r/min/
0 to 8000r/min *
1
,
9999
9999
34 Speed jump 2B
0 to 12000r/min/
0 to 8000r/min *
1
,
9999
9999
35 Speed jump 3A
0 to 12000r/min/
0 to 8000r/min *
1
,
9999
9999
36 Speed jump 3B
0 to 12000r/min/
0 to 8000r/min *
1
,
9999
9999
37 Speed display
0,
0.01 to 9998
0
40
RUN key rotation direction
selection
0, 1 0
41 Up-to-speed sensitivity 0 to 100% 10%
42 Speed detection
0 to 12000r/min/
0 to 8000r/min *
1
180r/min
43
Speed detection for reverse
rotation
0 to 12000r/min/
0 to 8000r/min *
1
,
9999
9999
44
Second acceleration/
deceleration time
0 to 3600s 5s
45 Second deceleration time
0 to 3600s,
9999
9999
48
Second stall prevention
operation current
0 to 200%,
9999
9999
52
DU/PU main display data
selection
0, 5, 8 to 12,
14, 20,
23 to 25,
52 to 55, 61,
62, 64, 100
0
54 FM terminal function selection
1 to 3, 5,
8 to 12, 14,
21, 24, 52,
53, 61, 62
1
55 Speed monitoring reference
0 to 12000r/min/
0 to 8000r/min *
1
3000r/min
56 Current monitoring reference 0 to 500A
Rated
motor
current
59 Remote function selection 0, 1, 2, 3 0
65 Retry selection 0 to 5 0
67
Number of retries at fault
occurrence
0 to 10,
101 to 110
0
68 Retry waiting time 0.1 to 600s 1s
69 Retry count display erase 0 0
70
Special regenerative brake duty
0 to 30% 0%
73 Analog input selection 0, 1, 10, 11 1
74 Input filter time constant 0 to 8 1
75
Reset selection/disconnected
PU detection/PU stop
selection
0 to 3,
14 to 17
14
77 Parameter write selection 0, 1, 2 0
78
Reverse rotation prevention
selection
0, 1, 2 0
79 Operation mode selection
0, 1, 2, 3, 4,
6, 7
0
117
PU communication station
number
0 to 31
(0 to 247)
0
118 PU communication speed
48, 96, 192,
384
192
119
PU communication stop bit length
0, 1, 10, 11 1
120
PU communication parity check
0, 1, 2 2
121
Number of PU communication
retries
0 to 10, 9999 1
122
PU communication check time
interval
0,
0.1 to 999.8s,
9999
0
123
PU communication waiting
time setting
0 to 150ms,
9999
9999
Parameter
Name
Setting
Range
Initial
Value