20
Start/stop from the operation panel (PU operation)
5.1.2 Using the setting dial like a potentiometer to perform operation
POINT
y Set "0" (extended parameter valid) in Pr. 160 Extended function display selection.
y Set "1" (setting dial potentiometer mode) in Pr. 161 Speed setting/key lock operation selection.
Operation example Change the speed from 0r/min to 1800r/min during operation
Operation
1.
Screen at power-ON
The monitor display appears.
2.
Operation mode change
Press to choose the PU operation mode. PU indicator is lit.
3.
Selecting the setting dial mode
Change the Pr. 160 setting to "0" and the Pr. 161 setting to "1".
(Refer to page 4 for change of the setting.)
4.
Start
Press to start the speed.
5.
Speed setting
Turn until " " (1800/min) appears. The flickering speed is the set speed.
You need not press .
REMARKS
y If flickering "1800" turns to "0", the Pr. 161 Speed setting/key lock operation selection setting may not be "1".
y Independently of whether the drive unit is running or at a stop, the speed can be set by merely turning the .
NOTE
y When setting speed by turning setting dial, the speed goes up to the set value of Pr. 1 Maximum setting (initial value:
3000r/min). Adjust Pr. 1 Maximum setting setting according to the application.