PowerTec DFS-1 Outboard Motor User Manual


 
Page 16
DFS-1 Manual Revised 7/95
POWERTEC Ind. Corp.©
FREQUENCY INPUTS AND
OUTPUTS
There is one frequency input and there are two
frequency outputs available.
INPUT
#1 REFERENCE FREQUENCY INPUT
TB2:A Terminals 11 (+) and 12 (-).
This is a line receiver type input which must be
driven by a differential line driver output.
This frequency input requires a frequency 16
times the feedback from the motor.
The feedback from the motor is normally 120
PPR for 4 pole motors and 240 PPR for 8 pole
motors.
Normal input is 56 Kilohertz for 0 to full speed
for a 1750 RPM motor with a 120ppr encoder.
Terminal 13 is for the shield. Do not ground
terminal 13 directly. It is internally terminated.
OUTPUTS
#1 REFERENCE FREQUENCY OUTPUT
TB2:B Terminals 10 (+) and 11 (-),
This is a differential line driver output which
must be used with a differential line driver input.
This frequency output is 16 times the reference
frequency to the motor.
This output may drive up to 32 receivers.
Connect the shield to terminal 12. This will
ground the shield internally.
#2 MOTOR SPEED FREQUENCY OUTPUT
TB2:B Terminals 13 (+) and 14 (common),
This output is a +24VDC peak square wave at
the motor feedback pulse rate, which is 2 times
RPM for 4 pole motors and 4 times RPM for 8
pole motors.
The reference frequency input and output are
capable of receiving and sending at up to 1 Mega-
hertz.
Motor Speed output emits frequencies up to 100
Kilohertz.
DIGITAL INPUTS
The eight digital inputs of the DFS-1 are
optically coupled requiring +24VDC (+/-6VDC) at
about 5mA each. These inputs are isolated from the
common of the board.
All inputs are programmable as to function,
EXCEPT the EMERGENCY STOP input. Inputs #1
through #7 may be assigned as general purpose
inputs.
The defaults are as follows:
TB2:A terminal 3(+) Emergency Stop
(Cannot be reassigned)
DI 1. TB2:A4(+) Run
DI 2. TB2:A5(+) Preset Speed
DI 3. TB2:A6(+) Up (Increase)
DI 4. TB2:A7(+) Down (Decrease)
DI 5. TB2:A8(+) Reverse
DI 6. TB2:A9(+) Frequency Mode
DI 7. TB2:A10(+) Local/Remote
Inputs #1 through #7 may also be programmed
for inverted input, i.e., active when input is low.
DIGITAL OUTPUTS
There are four dry contact outputs from the
DFS-1. All of these outputs are on TB2:B. All
outputs are programmable as to function, and all
outputs may be set up as either normally open or
normally closed.
Each relay output has a single, isolated, contact
output which may be programmed as normally open
or normally closed, with the contact rated at 1 Amp,
125VAC resistive.
The default assignments are as follows:
DO 1. TB2:B terminals 2 and 3 Run relay contact
Closed while running
DO 2. TB2:B terminals 4 and 5 No fault relay
Closed while no faults
DO 3. TB2:B terminals 6 and 7 At Speed relay
Closed when at speed
DO 4. TB2:B terminals 8 and 9 Remote Mode
Closed when in Remote