58. SLAVE JOG RATIO
USE PARAMETER #58 TO SET A JOG SPEED
WHICH CAN BE TOGGLED IN AND OUT.
RANGE OF VALUES: FFFE 7961h to 0001 869Fh
-99,999 to 99,999 (decimal)
Default Value: 0000 00C8h 100 (decimal)
The SLAVE JOG Speed is the speed to which
the motor will go when a JOG input is activated on
one of the Digital inputs (any of the seven digital
inputs may be programmed as a JOG input) when the
DFS-1 is in the SLAVE mode. If more than one input
is programmed as a JOG input, they must both be
present to activate the SLAVE JOG Speed function
(the inputs are logically ANDed).
59. EGU TAG SELECT
(Parameter 59 not functional at present)
RANGE OF VALUES: 0 TO F
0= UNK 6= LBS/HR
1= RPM 7= PCT
2= GPM 8= CFM
3= FPM 9= Y/MIN
4= SPM 10= M/MIN
5= LBS-FT 11= IN/SEC
Default Value: 0000 0000h 0 (decimal)
60. MASTER PRESET #2
USE PARAMETER #60 TO SET A PRESET SPEED
WHICH CAN BE TOGGLED IN AND OUT.
RANGE OF VALUES: FFFE 7961h to 0001 869Fh
-99,999 to 99,999 (decimal)
Default Value: 0000 00C8h 100 (decimal)
The MASTER PRESET #2 is the speed to which
the motor will go when a PRESET #2 input is
activated on one of the Digital inputs (any of the
seven digital inputs may be programmed as a
PRESET #2 input) when the DFS-1 is in the MAS-
TER mode. If more than one input is programmed as
a PRESET #2 input, they must both be present to
activate the MASTER PRESET #2 function (the
inputs are logically ANDed).
61. SLAVE PRESET #2
USE PARAMETER #61 TO SET A
PRESET SPEED WHICH CAN BE TOGGLED IN
AND OUT.
RANGE OF VALUES: FFFE 7961h to 0001 869Fh
-99,999 to 99,999 (decimal)
Default Value: 0000 00C8h 100 (decimal)
The SLAVE PRESET #2 is the speed to which
the motor will go when a PRESET #2 input is
activated on one of the Digital inputs (any of the
seven digital inputs may be programmed as a
PRESET #2 input) when the DFS-1 is in the SLAVE
mode. If more than one input is programmed as a
PRESET #2 input, they must both be present to
activate the SLAVE PRESET #2 function (the inputs
are logically ANDed).
62. CONTACTOR DELAY
USE PARAMETER #62 TO SET TIME
INTERVAL BETWEEN RUN COMMAND AND
INITIAL FIRING OF TRANSISTORS.
RANGE OF VALUES: 0000 0000 to 0000 0028h
0 TO 40 (decimal)
Default Value: 0000 0000h 0 (decimal)
This parameter sets the time interval between the
acceptance of a run command and the initial firing of
the transistors. If the Contactor Aux input does not
become active in this time period, the transistors will
not fire and the drive will return to a stop condition.
The value of this parameter is in increments of 25ms.
See the Additional Info section for examples.