Appendix C: Graco Gateway to ControlLogix via Ethernet IP
312785C 73
ControlLogix Configuration
1. Run the RSLogix 5000 program and create a new
configuration.
2. Add a 1756-ENET/B or a 1756-ENBT/A to your I/O
configuration. You will need to:
a. Switch to offline mode.
b. Right click on the I/O Configuration node in the
Controller Organizer view and choose Add Mod-
ule.
c. In the Select Module Type window, choose
1756-ENET/B or 1756-ENBT/A entry. RSLogix
will open the Module Properties window. See
F
IG. 69.
d. Enter the IP Address of the ENET/B or ENBT/A
interface.
e. Click Finish to add the interface to your I/O con-
figuration.
f. Download the configuration.
g. Switch to online mode and open the
1756-ENET/B or 1756-ENBT/A node proper-
ties under the I/O Configuration in the Controller
Organizer.
h. Select the Port Configuration Tab from the Mod-
ule Properties window. See F
IG. 70.
i. Enter the IP Address and Subnet Mask. The IP
Address must match the IP Address entered in
the Properties window (F
IG. 69).
j. Apply the settings using the Set button.
k. You can now verify the network module network
communications with your unit using suitable
diagnostic tools such as Ping.
3. Add the Graco Gateway to the RSLogix configura-
tion as follows:
a. Switch to offline mode.
b. Right click on the 1756-ENET/B or
1756-ENBT/A node under the I/O Configuration
in the Controller Organizer view and choose
Add Module.
c. In the Select Module Type window, choose
Generic Ethernet Module. See F
IG. 71.
d. Click OK. This will open the Module Properties
window. See F
IG. 72.
F
IG. 69. Ethernet Module Properties
IP Address
Finish Button