Gateway 312785C Marine Radio User Manual


 
Appendix C: Graco Gateway to ControlLogix via Ethernet IP
312785C 75
e. In the Name field, enter a descriptive name to
identify the module. See F
IG. 72.
f. In the Address/Host Name field, enter the IP
Address of the Graco Gateway.
g. Enter 2 in the Input Assembly Connection Point
and a size of 2. This will match a read only
Slave Gateway block configured in the Gateway,
and will be used for reading data from the Gate-
way to the ControlLogix.
h. Enter 3 in the Output Assembly Connection
Point and a size of 2. This will match a
read/write Slave Gateway block configured in
the Gateway, and will be used for writing data
from the ControlLogix to the Gateway.
i. Enter 1 in the Configuration Connection Point
and a size of 0. Configuration data is not sup-
ported by the Gateway.
j. Press Finish to add the Gateway to the I/O con-
figuration.
The connection points and sizes are arbitrary, as
long as the connection point, size, and direction are
matched in the configuration of the Gateway.
Connection point direction is always relative to the
originator, which in the case of the current Gateway
Ethernet/IP implementation is always the device and
never the Gateway. An input connection therefore
specifies data flow from the Gateway to the device,
and an output connection specifies data flow from
the device to the Gateway.
F
IG. 72. Ethernet Module Properties