Toshiba Single-phase 200V class 0.2 to 2.2kW Marine Battery User Manual


 
E6581090
K-5
11
  Operation mode parameters
Title
Communication
No.
Function Unit
Minimum setting unit
Panel/
Communication
Adjustment range
Default
setting
User
setting
Reference
H
0300 PWM carrier
frequency
--0:2kHz
1:2kHz (Random
mode)
2:4kHz
3:4kHz (Random
mode)
4:8kHzauto-reduction
mode
5:12kHz (auto-
reduction mode)
6:16kHz (auto-
reduction mode)
56.9
H 0301 Auto-restart control
selection
--0:Disabled
1:At auto-restart after
momentary stop
2:When turning ST-
CC on or off
3:At auto-restart after
momentary stop or
when turning ST-CC
on or off
06.10.1
H
0302 Regenerative power
ride-though control
--0:Disabled
1:Enabled
2:Deceleration stop
06.10.2
H 0303 Retry selection
(Number of times)
Times 1/1 0(OFF),1-1006.10.3
H
0305 Over voltage limit
operation
--0:Disabled
1:Enabled
2:Enabled (forced
shortened
deceleration)
06.10.4
H 0360 PI control - - 0: Disabled
1: Enabled
06.11
H 0362 Proportional (P) gain - 0.01/0.01 0.01-100.0 0.30 6.11
H 0363 Integral (I) gain - 0.01/0.01 0.01-100.0 0.20 6.11
  Torque boost parameters
Title
Communication
No.
Function Unit
Minimum setting
unit Panel/
Communication
Adjustment range
Default
setting
User
setting
Reference
H
0401 Slip frequency gain % 1/1 0-150 50 6.12.1
H
0409 Base frequency
voltage 1
V1/0.1 50-500 *2 6.12.1
H
0415 Motor rated current A 0.1/0.1 0.1-50.0 *3 6.12.2
H 0416 Motor no-load current % 1/1 30-80 *3 6.12.2
H
0417 Motor rated speed min
-1
1/1 100-12000 *2 6.12.2
H 0418 Speed control gain % 1/1 0-100 40 6.12.2
H
0419 Speed control stable
coefficient
%1/10-100 206.12.2
*2: The value is changed according to the set-up parameter condition.
(VFNC1 (S)-□□□□P-W type)
FH:80, UL80, VL:60, F127:0, F170:60, F171:200, F204:80, F409:200, F417:1710 for VFNC1 (S)-□□□
P type.
*3:Parameter values vary depending on the capacity. Refer to page K-8.