6
Output frequency [Hz]
Time [sec]
H
Low speed signal output: 4
FM/OUT terminal (
H
)
FL terminal (H)
ON
OFF
ON
OFF
0
Set frequency
Low speed reverse signal output: 5
FM/OUT terminal (
H
)
FL terminal (H)
* FM/OUT terminal function selection (HOUN) : 0 (Output frequency)
[Connection diagram]
P15
OUT
Ry
6.1.2 Output of specified speed reach si+gnal (output of arbitrarily set frequency)
H
: Speed-reach setting frequency (Hz)
H
: Output terminal selection 1 (FM/OUT)
HOUN
: FM/OUT terminal functions selection
H
: Output terminal selection 3 (FLA, FLB, FLC)
Function
If the output frequency exceeds the
H
-set frequency
±
2.5 Hz, an OFF signal will be put
out.
ڎ
The low speed signal output frequency function is assigned by default to the FM/OUT
terminal.
ڎ
Before using the FM/OUT terminal, you need to make a selection between meter (PWM)
output and open collector output.
To use the FM/OUT terminal as an open collector output terminal, set
HOUN
to -1 (open
collector output).
ڎ
Signals can be sent to the relay output terminals FLA, FLB and FLC by changing a
parameter setting.
Parameter for specifying a frequency
Title Function Adjustment range Default setting
H
Speed-reach setting frequency
(Hz)
0.0HJ (Hz) 0.0
 ■Related parameters
Title Function Adjustment range Default setting
HOUN
FM/OUT terminal functions
selection
-1: Open collector output
0: Output frequency
1: Output current
2: Frequency setting
3: Adjustment (current output
fixed at 100%)
4: Adjustment (current output
fixed at 50%)
5: Adjustment (output fixed at
the max frequency)
6: Adjustment (gain display)
0
H Output terminal selection 1 (FM/OUT) 0~13 (See 6.2.6 for details.) 4
H Output terminal selection 3 (FL) 0~13 (See 6.2.6 for details.) 10
If using the relay with the rated voltage DC12V of operating
coil, the maximum allowable voltage should be higher than
120% of rated voltage, and the maximum ampere value
should not exceed 50mA.