Toshiba Single-phase 200V class 0.2 to 2.2kW Marine Battery User Manual


 
E6581090
K-6
11
 
  
 
••
Acceleration/deceleration time parameters
Title
Communication
No.
Function Unit
Minimum setting
unit Panel/
Communication
Adjustment range
Default
setting
User
setting
Reference

0500 Acceleration time 2 s 0.1/0.1 0.1-3000 10.0 6.13

0501 Deceleration time 2 s 0.1/0.1 0.1-3000 10.0 6.13
 0505 Acceleration/decelerat
ion 1 and 2 switching
frequency
Hz 0.1/0.01 0- 0.0 6.13
 
  
 
••
Protection parameters
Title
Communication
No.
Function Unit
Minimum setting
unit Panel/
Communication
Adjustment range
Default
setting
User
setting
Reference
 0601 Stall prevention level % 1/1 30-199 (%)
200 (disabled)
150 6.14.1

0602 Inverter trip retention
selection
--0: Not retained,
1: Retained
06.14.2
 0603 External input trip stop
mode selection
--0:Coast stop
1:Slowdown stop
2:Emergency DC
braking
06.14.3
 0605 Output phase failure
detection mode
selection
--0:Disabled
1:Selected (Output
open-phase is
checked when
operation is started
for the first time after
power is turned on.)
2:Selected (Output
open-phase is
checked each time
operation is started.)
06.14.4

0607 Motor 150%-overload
time limit
s1/1
10800
300 6.14.5

0608 Input phase failure
detection mode
selection
--0: Disabled,
1: Enabled
16.14.6
 0616 Over-torque alarm
level
%10-200 150 6.14.7

0618 Over-torque detection
time
s0.10.0 (Disabled),
0.1-10.0
0.5 6.14.7

0627 Under voltage trip
selection
--0:Disabled
1:Enabled (64% or
less: Trip, FL relay
activated)
2:Disabled (50% or
less: Trip, FL relay
not activated)
06.14.8

0633 Analog input
disconnection
detection
%10 (Disabled), 1 - 100% 0 6.14.9