Toshiba Single-phase 200V class 0.2 to 2.2kW Marine Battery User Manual


 
E6581090
F-10
6
6.5 Operation frequency
6.5.1 Starting frequency
H
: Starting frequency setting (Hz)
Function
The frequency set with the H parameter is put out immediately after the completion of
frequency setting.
[Parameter setting]
Title FunctionAdjustment range Default setting
H Starting frequency setting (Hz)
0.510.0(Hz)
0.5
Starting frequency setting
H
Output frequency [Hz]
Time [sec]
0
6.5.2 Start/stop control by means of frequency setting signals
H
: Operation starting frequency (Hz)
H
: Operation starting frequency hysteresis (Hz)
Function
The start/stop of operation can be controlled, by simply using frequency setting signals.
[Parameter setting]
Title Function Adjustment range Default setting
H
Operation starting frequency
(Hz)
0.0HJ (Hz) 0.0
H
Operation starting frequency
hysteresis (Hz)
0.0HJ (Hz) 0.0
0 A B 100%  Frequency command value
H
H
H
HH
HJ
The inverter starts to accelerate when the
frequency setting signal reaches point B.
Deceleration starts when the frequency
setting signal falls below point A.
Output frequency [Hz]