Toshiba Single-phase 200V class 0.2 to 2.2kW Marine Battery User Manual


 
E6581090
M-3
13
(Continued)
Error
code
Alarm
code
Problem Possible causes Remedies
*
GRJ
0008 Input phase failure
A phase failure occurred in the
input line of the main circuit.
The inverter may trip because of
GRJ if switching between
acceleration and deceleration is
done in succession at intervals
of less than 1 second.
Check the main circuit input line
for phase failure.
Enable H (input phase
failure detection). Set the
H parameter to 0.
QJ 0010 Overheat
The cooling fan does not rotate.
The ambient temperature is too
high.
The vent is blocked up.
A heat generating device is
installed close to the inverter.
The thermistor in the unit is
broken.
Restart the operation by
resetting the inverter after it has
cooled down enough.
The fan requires replacement if
it does not rotate during
operation.
Secure sufficient space around
the inverter.
Do not place any heat-
generating device near the
inverter.
Make a service call.
WR
001E Undervoltage trip
(main circuit)
The input voltage (in the main
circuit) is too low.
Check the input voltage.
Enable H (undervoltage
trip selection).
To cope with a momentary stop
due to undervoltage, enable
H (ride-through control)
and H (auto-restart).
GH 0022 Ground fault trip
Arm overcurrent
A ground fault occurs in the
output cable or the motor.
A main circuit element is
defective.
Check the cable and the motor
for ground faults.
Make a service call.
G
0011 Emergency stop
During automatic operation or
remote operation, a stop
command is entered from the
operation panel or a remote
input device.
Reset the inverter.
GTT 0015 Main unit RAM fault
The control RAM is defective. Make a service call.
GTT 0016 Main unit ROM fault
The control ROM is defective. Make a service call.
GTT 0017 CPU fault trip
The control CPU is defective. Make a service call.
GTT
0018 Remote control
error
An error arises during remote
operation.
Check the remote control
device, cables, etc.
GTT
001A Current defector
fault
The current detector is defective. Make a service call.
GGR
0012 EEPROM fault 1
A data writing error occurs. Turn off the inverter, then turn it
on again. If it does not recover
from the error, make a service
call.
GGR 0013 EEPROM fault 2
Power supply is cut off during
V[R operation and data
writing is aborted.
Turn the power off temporarily
and turn it back on, and then try
V[R operation again.
GGR
0014 EEPROM fault 3
A data writing error occurs. Turn off the inverter, then turn it
on again. If it does not recover
from the error, make a service
call.
*
G
0032 Break in analog
signal cable
The signal input via VI/S3 is
below the analog signal
detection level set with H.
Check the cables for breaks
and change the setting of
H if no breaks are found.
(Continued overleaf)