Toshiba Single-phase 200V class 0.2 to 2.2kW Marine Battery User Manual


 
E6581090
E-1
5
5. Basic parameters
Basic parameters refer to parameters you have to set first before using the inverter.
5.1 Selecting an operation mode
 : Command mode selection
 : Frequency setting mode selection
<Command mode selection>
Title Function Adjustment range Default setting

Command mode
selection
0: Terminal block
1: Operation panel
1
[Settings]
: A Run or Stop command is entered by inputting an ON or OFF signal from an
external control device.
: A Run or Stop command is entered by pressing the or key on
the operation panel.
(When an optional expansion operation panel is used)
* There are two kinds of functions: function of responding to signals from the device specified with
the  parameter, and function of responding to singles from the terminal board only.
External input signal Function
Input terminal function 12 (PNL/TB) OFF Operation panel operation
=1
Input terminal function 12 (PNL/TB) ON Terminal board operation
* When the highest-priority command is entered from an external control device or a terminal
block, it takes priority over commands from the device specified with the  parameter.
<Frequency setting mode selection>
Title Function Adjustment range Default setting

Frequency setting
mode selection
0 : Terminal block
1 : Operation panel
2 : Internal potentiometer
3 : Serial communications (with an optional control
device)
4 : Terminal block/internal potentiometer switching
2
[Settings]
: 外部信号 A frequency setting command is entered by inputting a signal* from an
external control device. (*: VI/S3 terminal: 0~(5)10Vdc or 4~20mAdc)
: The operation frequency is set by pressing the or key on the
operation panel or an expansion operation panel (optional).
: The operation frequency is set using the internal potentiometer built into the
inverter. Turning the knob clockwise increases the frequency.
: The operation frequency is set by serial communications with an optional
control device.
: Switching between frequency setting by means of analog signals and that by
means of the internal potentiometer is done by activating or deactivating the
input terminals (multi-function programmable input terminals).
Function
 (command mode selection) :
Used to select a mode of entering Run and Stop commands from the inverter (operation
panel or terminal board).
 (frequency setting mode selection) :
Used to select a mode of entering frequency setting commands from the inverter (internal
potentiometer, operation panel, terminal board, serial communications with an external
control device, or internal potentiometer/terminal board switching).
Terminal bloc
k
o
p
eration
Operation panel
o
p
eration
RUN
STOP
Terminal block
Operation panel
Potentiometer
Terminal block/
internal
potentiometer
Serial
communications