E6581090
E-1
5
5. Basic parameters
Basic parameters refer to parameters you have to set first before using the inverter.
5.1 Selecting an operation mode
: Command mode selection
: Frequency setting mode selection
<Command mode selection>
Title Function Adjustment range Default setting
Command mode
selection
0: Terminal block
1: Operation panel
1
[Settings]
: A Run or Stop command is entered by inputting an ON or OFF signal from an
external control device.
: A Run or Stop command is entered by pressing the or key on
the operation panel.
(When an optional expansion operation panel is used)
* There are two kinds of functions: function of responding to signals from the device specified with
the parameter, and function of responding to singles from the terminal board only.
External input signal Function
Input terminal function 12 (PNL/TB) OFF Operation panel operation
=1
Input terminal function 12 (PNL/TB) ON Terminal board operation
* When the highest-priority command is entered from an external control device or a terminal
block, it takes priority over commands from the device specified with the parameter.
<Frequency setting mode selection>
Title Function Adjustment range Default setting
Frequency setting
mode selection
0 : Terminal block
1 : Operation panel
2 : Internal potentiometer
3 : Serial communications (with an optional control
device)
4 : Terminal block/internal potentiometer switching
2
[Settings]
: 外部信号 A frequency setting command is entered by inputting a signal* from an
external control device. (*: VI/S3 terminal: 0~(5)10Vdc or 4~20mAdc)
: The operation frequency is set by pressing the or key on the
operation panel or an expansion operation panel (optional).
: The operation frequency is set using the internal potentiometer built into the
inverter. Turning the knob clockwise increases the frequency.
: The operation frequency is set by serial communications with an optional
control device.
: Switching between frequency setting by means of analog signals and that by
means of the internal potentiometer is done by activating or deactivating the
input terminals (multi-function programmable input terminals).
• Function
(command mode selection) :
Used to select a mode of entering Run and Stop commands from the inverter (operation
panel or terminal board).
(frequency setting mode selection) :
Used to select a mode of entering frequency setting commands from the inverter (internal
potentiometer, operation panel, terminal board, serial communications with an external
control device, or internal potentiometer/terminal board switching).
Terminal bloc
k
o
p
eration
Operation panel
o
p
eration
RUN
STOP
▲
▼
Terminal block
Operation panel
Potentiometer
Terminal block/
internal
potentiometer
Serial
communications