Dell XC730xd Life Jacket User Manual


 
Physical
Storage 5% to 95% RH with 33°C (91°F) maximumdew
point. Atmosphere must be non-condensing at all
times.
Operating 10% to 80% Relative Humidity with 29°C
(84.2°F)maximum dew point.
Maximum vibration
Operating 0.26 G
rms
at 5 Hz to 350 Hz(all operation
orientations).
Storage 1.88 G
rms
at 10 Hz to 500Hz for 15 min (all six
sides tested).
Maximum shock
Operating Six consecutively run shock pulses in the positive
and negative x, y, and z axes of 40 G for up to 2.3
ms.
Storage Six consecutively run shock pulses in the positive
and negative x, y, and z axes (one pulse on each
side of the system) of 71 G for up to 2 ms.
Maximum altitude
Operating
3048 m (10,000 ft).
Storage 12,000 m (39,370 ft).
Operating temperature de-rating
Up to 35 °C (95 °F) Maximum temperature is reduced by 1°C/300m
(1°F/547 ft) above 950 m (3,117 ft).
35 °C to 40 °C (95 °F to 104 °F) Maximum temperature is reduced by 1°C/175m
(1°F/319 ft) above 950 m (3,117 ft).
40 °C to 45 °C (104 °F to 113 °F) Maximum temperature is reduced by 1°C/125m
(1°F/228 ft) above 950 m (3,117 ft).
Particulate contamination
NOTE: This section defines the limits to help avoid IT equipment damage and/or failure from
particulates and gaseous contamination. If it is determined that levels of particulates or gaseous
pollution are beyond the limits specified below and are the reason for the damage and/or failures
to your equipment, it may be necessary for you tore-mediate the environmental conditions that are
causing the damage and/or failures. Re-mediation of environmental conditions is the responsibility
of the customer.
Air filtration Data center air filtration as defined by ISO Class 8
per ISO 14644-1 with a 95% upper confidence
limit.
NOTE: Air entering the datacenter must have
MERV11 or MERV13 filtration.
153