156
Using FINS Message Communications Section 6-3
Example 2: Sending a FINS Command Using CMND
Operation
The PC with DeviceNet Unit 1 with node address 5 reads the data from
the 5 words D01000 to D01004 from the PC with DeviceNet Unit 2 with
node address 06.
The MEMORY AREA READ command (01 01) is used to read variable
data.
Command data is written starting from D01000 in the PC with De-
viceNet Unit 1 with node address 5 and the response data is written
starting from D02000.
The completion code is stored in D00006 when execution of SEND
has been completed.
Command Details
The following command is used: [CMND S D C]
S = D01000: First command word at local node
Settings (Hex)
D01000 = 0101: Command Code
D01001 = 8203: Command parameters
D01002 = E800: Command parameters
D01003 = 0005: Command parameters
D = D02000: First response word at local node
C = D00000: First control word
Settings (Hex).
D00000 = 0008: Number of command bytes
D00001 = 000E: Number of response bytes
D00002 = 0001: Destination network address
D00003 = 0600: Destination node address (06)
Destination unit address (00 = CPU Unit)
D00004 = 0000: Response, communications port 0, no retries
D00005 = 0064: Response monitoring time
CS/CJ-series
DeviceNet Unit No. 0
CPU
Unit
Node 05
Network 01
CMND
Node 06
Unit ad-
dress: 00
CPU
Unit
CS/CJ-series
DeviceNet Unit
MEMORY AREA READ command