Omron CS1W-DRM21 Marine RADAR User Manual


 
183
Connecting to the CX-Programmer via the DeviceNet Section 7-1
7-1-1 Setting Node Addresses
When the CX-Programmer is connected online, it uses FINS message com-
munications. It is thus necessary to set the node address to a number other
than 0 for DeviceNet Units mounted to the target PC, DeviceNet Units
mounted to a PC which is connected by a serial connection to the CX-Pro-
grammer, or DeviceNet Units mounted to a PC relaying between networks.
If a DeviceNet Unit with the address node 0 exists in the online connection
path, connection will not be possible.
7-1-2 Setting the Message Monitoring Timer of the DeviceNet Unit
When connecting the CX-Programmer via the DeviceNet, set the message
monitoring timer inside the following DeviceNet Units to 20,000 ms (20 s).
The DeviceNet Unit mounted to the PC with the serial connection to the
CX-Programmer.
The DeviceNet Unit mounted to the PC relaying between networks.
Use the Configurator to set the message monitoring timer.
Setting the Message
Monitoring Timer
Use the following procedure to set the message monitoring timer.
1,2,3... 1. Select Device/Parameter/Edit and then click the Message Timer Tab.
DeviceNet
DeviceNet
Ethernet
DeviceNet Unit
CX-Programmer Ver.
2.1 or later
CX-Programmer Ver.
2.1 or later
Serial connection (Host
Link or peripheral bus)
Ethernet Unit
DeviceNet Unit
Set the message
monitoring timer of
this DeviceNet Unit
to 20,000 ms (20 s).
Set the message
monitoring timer of this
DeviceNet Unit to
20,000 ms (20 s).