Omron CS1W-DRM21 Marine RADAR User Manual


 
249
Memory Card Backup Functions Appendix D
3. Saving Files from Configurator to Memory Card
Device parameter files (.dvf files) for this DeviceNet Unit that have been created using the Configurator can be
saved on the Memory Card via the HMC-AP001 Memory Card Adaptor as file name DNnnBKUP.dvf (where nn
is the Unit number in 2-digit hexadecimal). This DeviceNet Unit can be mounted to the CPU Unit and, by turn-
ing ON the Unit Setup File Restore Switch (word n, bit 14), the setup data can be restored to the DeviceNet
Unit.
Note The file name when saving setup data to the Memory Card must be DNnnBKUP.dvf (where nn is the Unit
number in 2-digit hexadecimal). For example, for unit number 00, the file name must be DN00BKUP.dvf.
If the file is saved under another name, the data cannot be restored from the Memory Card to the
DeviceNet Unit.
File Names
The following files are created on the Memory Card.
Directory (fixed): Route and directory.
File name (fixed): DNnnBKUP.dvf (nn: Unit number in 2-digit hexadecimal).
Note The data in the above files is compatible with the data in the DeviceNet Unit device parameter file.
DeviceNet Unit
All
setup
data
CPU Unit
Restore
Unit Setup File Restore Switch
Memory Card
Saved as file name DNnnBKUP.dvf, where nn
is the Unit number in 2-digit hexadecimal.)
Configurator (com-
puter)
Memory Card
HMC-AP001 Memory Card Adaptor
Saving device
parameter file