Sending Explicit Messages Section 6-4
When connecting networks, routing tables must be registered for the PC CPU
Units on all networks.
When connecting two or more communication units (including the DeviceNet
Unit) to a CS/CJ-series CPU Unit, the DeviceNet Unit must be registered in
the CS/CJ-series PC CPU Unit routing table (for the local network table only).
Commands cannot be executed if the DeviceNet Unit is not registered.
6-4 Sending Explicit Messages
CS/CJ-series DeviceNet Units can send explicit messages. FINS command
headers are attached to explicit messages and sent. Explicit messages can
be sent to the following destinations.
Masters or slaves made by other manufacturers
Other PCs with a CS/CJ-series DeviceNet Unit.
PCs (Slaves) with C200H I/O Link Units (See note).
Note Only reading and writing I/O memory is possible for PCs with C200H
I/O Link Units. Status reading/writing is not possible.
Example
Up to 3 levels of networks, including DeviceNet, are possible.
Controller Link Unit
Controller Link Unit
CS/CJ-series DeviceNet Unit
CS/CJ-series CPU Unit
Remote I/O communications
Controller Link
DeviceNet
CS/CJ-series DeviceNet Unit
DeviceNet
CS/CJ-series
DeviceNet Unit
CS/CJ-series DeviceNet Unit
CS/CJ-series CPU Unit
Explicit messages can be sent
Explicit message
FINS header
DeviceNet
Other manufacturer master or slave
or
C200H I/O Link Unit
C200HX/HG/HE or
CS/CJ-series
CPU Unit (Slave)
Note: Only I/O memory
read/write possible
CS/CJ-series DeviceNet Unit