Compaq ProLiant 3000 Servers Setup and Installation Guide
For use with 350-MHz or greater Intel processor-based servers only
Writer: Cheri Stewart Project: Compaq ProLiant 3000 Servers Setup and Installation Guide Comments: 179776-002
File Name: D-CH03.DOC Last Saved On: 1/12/99 1:24 PM
COMPAQ CONFIDENTIAL - NEED TO KNOW REQUIRED
Rack Temperature Requirements
The operating temperature inside the rack will always be higher than the room
temperature, and is dependent on the configuration of equipment in your rack.
The TMRA for each piece of equipment should be checked before installation.
The maximum internal rack temperature for your configuration should not
exceed the values shown in the following table:
Table 3-1
Rack Internal Temperature Maximums
Equipment Included Maximum Internal Rack Temperature
Rack-Mountable ProLiant Servers 50°C/122°F
Compaq Rack-Mountable options 40°C/104°F
Other manufacturers' options See other manufacturer’s specifications
CAUTION:
To reduce the risk of damage to the equipment when
installing third-party options:
Make sure that the option equipment does not impede
airflow to the Rack-Mountable ProLiant Servers or increase
the internal rack temperature beyond the Compaq specified
maximum rating.
Make sure that the Manufacturer’s Maximum Recommended
Ambient Operating Temperature of the option equipment is
not exceeded when installed in the rack.