Wait approximately 10 seconds for the system boot to begin. When the system begins to boot, the CABINET
FAULT and component lights flash on and off. As the booting progresses, the logic suitcase lights are
illuminated in the sequence listed (See Logic Suitcase Power-Up Light Sequence) .
Logic Suitcase Power-Up Light Sequence
Power-UpStage Color State Meaning
1
Red
Yellow
Green
Off
On
Off
The logic suitcase is performing its self-test.
2
Red
Yellow
Green
Off
Flashing
Off
The master logic suitcase has passed its self-test and is being configured by the system.
3
Red
Yellow
Green
Off
Off
On
The master logic suitcase and its partner are online and duplexed.
Stages 1 and 2 should last no longer than five minutes. If they last longer, turn off the system power switches
and the system console, wait about two minutes, and then turn on the power switches and system console to
begin the boot process again. If there is still a problem, refer to FTX System Administrator’s Guide:General