Trane WSHP-PRC001-EN Marine Sanitation System User Manual


 
WSHP-PRC001-EN 37
Performance Data
ARI-ISO (WLHP/GLHP)
Table P1: ARI-ISO WLHP and GLHP Performance
Rated in accordance with ISO Standard 13256-1: 1998 (Water Loop Heat Pumps and Ground Loop
Heat Pumps).
Certified conditions are 86°F EWT, 80.6°F DB/66.2°F WB EAT in cooling and 68°F EWT, 68°F DB/59°F
WB EAT in heating. Data shown is for application performance only, as these conditions are typical
for WSHP systems.
Models with capacities greater than 135,000 BTUH are not included in the ARI water-to-air and
brine-to-air heat pump certification program.
Unit Size Rated Water
Flow
(GPM)
Rated Air
Flow
(SCFM)
Cooling
Capacity
WLHP
(BTUH)
EER
WLHP
Heating
Capacity
WLHP
(BTUH)
COP
WLHP
Cooling
Capacity
GLHP
(BTUH)
EER
GLHP
Heating
Capacity
GLHP
(BTUH)
COP
GLHP
006 1.5 190 7060 13.0 8160 4.3 6980 14.4 4690 3.1
009 2.1 285 8760 12.85 10900 4.6 8710 14.5 6100 3.1
012 2.8 380 12500 13.15 13200 4.35 12400 14.2 8700 3.2
015 3.5 460 14100 14.0 17200 4.8 14200 16.0 10200 3.45
018 4.2 570 19100 13.5 21600 4.45 18900 14.9 13000 3.15
024 5.5 760 25800 12.6 30400 4.35 26000 13.8 17800 3.25
030 6.9 900 28500 12.5 33100 4.25 28700 13.5 19800 3.1
036 8.3 1140 36000 13.7 41800 4.7 35200 14.5 22200 3.25
GEV 040 9.2 1200 38500 12.75 44200 4.2 38500 13.6 26100 3.1
042 9.7 1330 40200 12.05 47500 4.2 41700 13.4 27400 3.1
048 11.0 1520 49000 12.75 55300 4.25 49000 13.65 32000 3.1
060 14.5 1900 59300 12.8 72300 4.4 58500 13.75 43300 3.1