Table P38: 006-060 Correction Factors for Variation in Entering Air Temperature
* = Sensible equals total capacity
Cooling
Entering
Air WB F
Cooling
Capacity
Cooling
Input
Watts
Sensible vs Entering Dry Bulb
Multipliers
Heating
Entering
Air DB F
Heating
Capacity
Heating
Input
Watts
65.6 70.6 75.6 80.6 85.6
49.40.7220.893***** 53.01.0300.878
56.3 0.836 0.937 0.799 0.964 * * * 58.0 1.020 0.919
60.3 0.903 0.963 0.641 0.841 1.016 1.097 * 63.0 1.010 0.959
63.2 0.951 0.981 0.504 0.728 0.924 1.097 * 68.0 1.000 1.000
66.2 1.000 1.000 0.593 0.809 1.000 1.169 73.0 0.990 1.041
72.1 1.098 1.038 0.538 0.761 0.960 78.0 0.980 1.081
77.1 1.181 1.069 0.519 0.741 83.0 0.970 1.122