Trane WSHP-PRC001-EN Marine Sanitation System User Manual


 
62 WSHP-PRC001-EN
Table P38: 006-060 Correction Factors for Variation in Entering Air Temperature
* = Sensible equals total capacity
Cooling
Entering
Air WB F
Cooling
Capacity
Cooling
Input
Watts
Sensible vs Entering Dry Bulb
Multipliers
Heating
Entering
Air DB F
Heating
Capacity
Heating
Input
Watts
65.6 70.6 75.6 80.6 85.6
49.40.7220.893***** 53.01.0300.878
56.3 0.836 0.937 0.799 0.964 * * * 58.0 1.020 0.919
60.3 0.903 0.963 0.641 0.841 1.016 1.097 * 63.0 1.010 0.959
63.2 0.951 0.981 0.504 0.728 0.924 1.097 * 68.0 1.000 1.000
66.2 1.000 1.000 0.593 0.809 1.000 1.169 73.0 0.990 1.041
72.1 1.098 1.038 0.538 0.761 0.960 78.0 0.980 1.081
77.1 1.181 1.069 0.519 0.741 83.0 0.970 1.122
Performance Data
Correction Factors