Emerson Process Management LF-Series Marine Sanitation System User Manual


 
LF-Series Flowmeters: Sensor/Transmitter Installation 15
Installing the Field-Mount Transmitter
Installing the Sensor Installing the DIN TransmitterInstalling the FM TransmitterBefore You Begin
To rotate the display, follow the instructions below:
1. Power down the transmitter.
2. Remove the end-cap clamp by removing the cap screw. See Figure 3-5.
3. Turn the display cover counterclockwise to remove it from the main enclosure.
4. Carefully loosen (and remove if necessary) the semicaptive display screws while holding the
display module in place.
5. Carefully pull the display module out of the main enclosure until the sub-bezel pin terminals
are disengaged from the display module.
6. Rotate the display module to the desired position.
7. Insert the sub-bezel pin terminals into the display module pin holes to secure the display in its
new position.
8. If you have removed the display screws, line them up with the matching holes on the sub-
bezel, then reinsert and tighten them.
9. Place the display cover onto the main enclosure. Turn the display cover clockwise until it is
snug.
10. Replace the end-cap clamp by reinserting and tightening the cap screw.
11. Restore power to the transmitter.
WARNING
Using a dry cloth to clean the display cover can cause static discharge,
which could result in an explosion in an explosive atmosphere.
To reduce the risk of an explosion, always use a damp cloth to clean the display
cover in an explosive atmosphere.