Schneider Electric PM5100 Marine Instruments User Manual


 
PowerLogic™ PM5100 series user guide Chapter 3—Hardware Reference
© 2014 Schneider Electric All Rights Reserved 15
Power Factor Class 0.5 as per IEC 61557-12
1
Voltage Harmonics Class 5 as per IEC 61557-12
1
Voltage THD/thd Class 5 as per IEC 61557-12
1
Current Harmonics Class 5 as per IEC 61557-12
1
Current THD/thd Class 5 as per IEC 61557-12
1
MID Directive (2004/22/EC) Annex B and Annex D (PM5111) Class C
Input-voltage (up to 1.0 MV AC max, with voltage transformer)
Nominal Measured Voltage range
UL: 20-347 V L-N/35-600 V L-L
IEC: 20-400 V L-N/35-690 V L-L
(absolute range 35 V L-L to 760 V L-L)
Impedance 5 M
F nom 50/60 Hz
Input-current (configurable for 1 or 5 A secondary CTs)
I nom 5 A
Measured Amps with over range and Crest Factor
Starting current: 5mA
Operating range: 50mA to 8.5A
Withstand Continuous 20 A,10s/hr 50 A, 1s/hr 500 A
Impedance < 0.3 m
F nom 50/60 Hz
Burden <0.026VA at 8.5A
Frequency measurement
Measurement range 45 to 65 Hz
AC control power
Operating range
100 - 277 V AC L-N / 415 V L-L +/-10%
CAT III 300V class per IEC 61010
Burden <5 W,11 VA at 415 V L-L
Frequency 45 to 65 Hz
Ride-through time
80 mS typical at 120V AC and maximum burden.
100 mS typical at 230 V AC and maximum burden
100 mS typical at 415 V AC and maximum burden
DC control power
Operating range 125-250 V DC ±20%
Burden <4 W at 250 V DC
Ride-through time 50 mS typical at 125 V DC and maximum burden
Outputs
Digital output
Max load voltage 40 V DC
Max load current 20 mA
On Resistance 50 max
Meter constant
from 1 to 9,999,999 pulses per k_h (k_h = kWh,
kVARh or kVAh depending on the energy parameter
selected)
Pulse width for Digital Output 50% duty cycle
Pulse frequency for Digital Output 25 Hz max.
Leakage current 0.03 micro Amps
Isolation 5 kV rms
Optical outputs
Pulse width (LED) 200
s
Pulse frequency 50 Hz. max.
Meter constant from 1 to 9,999,999 pulses per k_h
Mechanical Characteristics
Product weight 380 g
IP degree of protection (IEC 60529) IP52 front display, IP30 meter body
Dimensions W x H x D [protrusion from cabinet]
96 x 96 x 72mm (depth of meter from housing
mounting flange) [13mm]
Mounting position Vertical
Panel thickness 6 mm maximum
Environmental Characteristics
Operating temperature
Meter -25 °C to +70 °C
Display (Display functions to -25º with reduced
performance)
-25 °C to +70 °C
Storage temp. -40 °C to +85 °C
Humidity range 5 to 95% RH at 50 °C (non-condensing)