PowerLogic™ PM5100 series user guide Chapter 3—Hardware Reference
© 2014 Schneider Electric All Rights Reserved 19
Meter wiring
For wiring instructions and safety precautions, see the meter installation sheet that was
shipped with your meter, or download a copy at www.schneider-electric.com.
• Wire connections to the meter’s voltage inputs, control power, digital output, and RS-
485 communications are terminated using the supplied pluggable wire connectors.
• When wiring the meter’s current inputs, terminate the wire ends with ring or split-ring
crimp connectors.
Use the meter installation sheet when wiring the meter.
Serial No. Description Specification
Voltage Inputs (V1, V2, V3, VN)
• Wire size: 0.82 - 3.31 mm
2
(18 - 12 AWG)
• Wire strip length: 0.28 in (7 mm)
• Torque: 0.5 - 0.6 N·m (4.4 - 5.3 in·lb)
• Screw driver type: M3
Control Power (L1, L2)
• Wire size: 0.82 - 3.31 mm
2
(18 - 12 AWG)
• Wire strip length: 0.28 in (7 mm)
• Torque: 0.5 - 0.6 N·m (4.4 - 5.3 in·lb)
• Screw driver type: M3
Digital Output (D1+, -/C)
• Wire size: 0.33 - 3.31 mm
2
(22 - 12 AWG)
• Wire strip length: 0.24 in (6 mm)
• Torque: 0.5 - 0.6 N·m (4.4 - 5.3 in·lb)
• Screw driver type: M2
Current Inputs
(I
1+
, I
1-
, I
2+
, I
2-
, I
3+
, I
3-
)
• Wire size: 0.82 - 3.31 mm
2
(18 - 12 AWG)
• Wire strip length:0.28 in (7 mm)
• Torque: 0.9 - 1.0 N·m (8.0 - 9.0 in·lb)
• Screw driver type: PH1
Modbus RS-485 (+,-, , C)
• Wire size: 0.33 - 3.31 mm
2
(22 - 12 AWG)
• Wire strip length: 0.24 in (6 mm)
• Torque: 0.5 - 0.6 N·m (4.4 - 5.3 in·lb)
• Screw driver type: M3
RS-485
Modbus
Modbus
RS-485
D1 = Rx+,Tx+
D0 = Rx-, Tx-
0V
_
+
I
1+
I
1-
I
2+
I
2-
I
3+
I
3-
+
_
UL: CAT III
20-347VLN/35-600VLL
IEC: CAT III
20-400VLN/35-690VLL