Schneider Electric PM5100 Marine Instruments User Manual


 
PowerLogic™ PM5100 series Chapter 13—MID Compliance
© 2014 Schneider Electric All Rights Reserved 89
Setting up the PM5111
You must configure all the lock-protected setup parameters before locking the meter.
When the meter is locked, those setup parameters cannot be edited.
Basic setup menu
See “Configuring the basic setup parameters” on page 32 to perform basic setup.
For MID compliance, the Power System must be set to one of the following settings:
3PH4W Wye Gnd (three-phase 4-wire wye grounded)
3PH3W Wye Ungnd (three-phase 3-wire wye ungrounded)
Advanced setup menu
See “Advanced setup” on page 38 to perform advanced setup.
You must use ION Setup to edit the device label.
Clock setup menu
See “Setting the clock” on page 37 to change the meter time using the display.
You can also use ION Setup to set or sync the meter time.
Passwords setup menu
See “Setting up the screen passwords” on page 36 to change the meter screen
passwords.
Initializing the meter
Initializing the meter clears the meter’s logged data, counters and timers. It is common
practice to initialize the meter after its configuration is complete, before adding it to an
energy management system.
1. After configuring all the meter setup parameters, navigate through the different
meter display screens and make sure the displayed data is valid.
2. See “Meter resets” on page 77 for instructions on clearing the meter’s recorded
logged data, counters and timers.
3. Select Meter Initialization to clear all recorded data.
Locking or unlocking the meter
After you initialize the meter, you must lock it in order to conform to MID standards.
1. Navigate to Maint > Setup > Meter >Lock.
2. Press Edit to activate or deactivate the lock.
Lock-protected functions
Menu Sub-menu Lock-protected function
Resets
Global Resets
Meter Initialization (all)
•Energies
Single Resets Energy