Schneider Electric PM5100 Marine Instruments User Manual


 
PowerLogic™ PM5100 series user guide Chapter 3—Hardware Reference
© 2014 Schneider Electric All Rights Reserved 27
Related topics
To configure RS-485 communications, see “Setting up serial communications” on
page 34.
Digital outputs
The meter is equipped with a digital output port (D1). You can configure the digital output
for use in the following application:
energy pulsing applications, where a receiving device determines energy usage by
counting the k_h pulses (k_h = kWh, kVARh or kVAh depending on the energy
parameter selected) coming from the meter’s digital output port.
The digital output can handle voltages less than 40 V DC. For higher voltage applications,
use an external relay in the switching circuit.
Related topics
See “Digital output applications” on page 47 for digital output use and configuration
details.
Digital output connections
D1 -/C
(60)
(57)
LOAD
< 20mA
< 40Vdc