PowerLogic™ PM5100 series user guide Chapter 4—Front panel display and meter setup
© 2014 Schneider Electric All Rights Reserved 39
7. Press Yes to save your changes.
Related topics
See“Total Harmonic Distortion and Total Demand Distortion” on page 67 for details
on how the meter calculates TDD.
Setting up the alarm / energy pulsing LED
The LED setup screen allows you to configure the alarm / energy pulsing LED for
alarming or energy pulsing application.
1. Navigate to Maint > Setup.
2. Enter the setup password (default is “0000”), then press OK.
3. Navigate to I/O > LED.
4. Press Edit.
5. Press or to modify the parameter as required, then press OK.
6. Press to exit. Press Yes to save your changes.
Advanced setup parameters
Parameter Values Description
Label -----
This label identifies the device, e.g., “Power
Meter”. You cannot use the front panel to edit
this parameter. Use ION Setup to change the
device label.
Load Timer Setpt (A) 0 - 99999
Specifies the minimum average current at the
load before the timer starts. The meter begins
counting the operating time whenever the
readings are equal to or above this average
current threshold.
Pk I dmd for TDD (A) 0 - 99999
Specifies the minimum peak current demand
at the load for inclusion in total demand
distortion (TDD) calculations. If the load
current is below the minimum peak current
demand threshold, the meter does not use the
readings to calculate TDD. Set this to “0”
(zero) if you want the power meter to use the
metered peak current demand for this
calculation.
Alarm / energy pulsing LED settings menu tree
LED setup parameter
Parameter Values Description
Mode Off, Alarm, Energy
Off disables the LED.
Alarm sets the LED for alarm notification.
Energy sets the LED for energy pulsing.
Maint
Reset
Setup
Meter
Comm
Alarm
HMI
Clock
LED
I/O
D out